MTN6700-0116 Schneider 16-channel KNX Hybrid Switch with manual mode:
MTN6700-0116 Schneider 16-channel KNX Hybrid Switch Specifications:
Version : light grey
Art. no : MTN6700-0116
Power supply: KNX Bus
KNX power consumption: < 840 mW
Nominal voltage: AC 250 V, 50/60 Hz
Rated current: 10 mA, maximum 26 mA/24 V
Nominal power for each contact:
AC1 10 A operation (cos φ = 0.8) accord. with IEC 60947-4-1
AC3 6 A operation (cos φ = 0.45) accord. with IEC 60947-4-1
Incandescent lamp: 2500 W
Fluorescent lamp: 2500 W
Electronic transformer for extra low voltage lamps (e.g. halogen lamps): 1100 W
Iron core transformer for extra low voltage lamps (e.g. halogen lamps): 900 W
LED lamp: 300 W, cos φ ≥ 0.6
Capacitive loads: 10 AX, 140 μF
Motors: 1500 VA, cos φ ≥ 0.6
Minimum switching current: 100 mA/12 V AC
Connection KNX: Bus connection terminal
Connection port mains: screw terminal blocks, 4x 8-gang
Relay data:
Protection class: II
Protection type: IP20
Inrush current: 320 A/2 ms
Mechanical service life: >100000
Switching frequency at rated load: Maximum 60 operation/min
Insulation category: Overvoltage category III, pollution degree 2
Environmental conditions
Operating temperature: -5…+45 °C
Storage temperature: -25 …+55 °C
Transport temperature: -25 …+70°C
Maximum humidity: 93 %, no condensation
Installation height: As high as 2000 m above sea level
Dimensions (WxHxD): 216x90x64 mm
MTN6700-0116 Schneider 16-channel KNX Hybrid Switch with manual mode:
For independent switching of 16 loads or for controlling up to 8 blinds/roller shutters, 4 fan coils with 3 levels, eight 2-pipe valve controls or four 4-pipe valve control. All functions are freely configurable and can be operated manually with a switch on the device.
A green LED indicates readiness for operation after the application has been loaded.
For mounting on DIN rails TH35 according to EN61715. The bus connection is made via a bus connection terminal.
MTN6700-0116 Schneider 16-channel KNX Hybrid Switch General KNX software functions:
Live signal, enabling safety priority function, central control of switching/curtains function, sending delay after bus voltage recovery
MTN6700-0116 Schneider 16-channel KNX Hybrid Switch Switching actuator functions:
Preset, Logic, Scene, Threshold, Safety, Forced, Locking, Central, Time function for each channel including delay, flashing and staircase timer, relay state after bus voltage failure/recovery/ETS download, object value of the Switch object after voltage recovery, status feedback for each channel
MTN6700-0116 Schneider 16-channel KNX Hybrid Switch Heating actuator functions:
PWM cycle time for continuous, 1 bit/1 byte control telegram, Valve protection, Safety, Locking, Forced, Cyclic surveillance, Operation as NC/NO, Valve position after bus voltage failure or recovery, Contact response value when contact is opened or closed
Contents: With bus connecting terminal and cable cover.